How to Calculate Sensible Heat Ratio

Calculate sensible heat ratio by dividing sensible cooling load by total sensible-plus-latent load on the same boundary. Include a separate fan-heat term only when that heat belongs on the selected boundary and has not already been counted.

Open the Sensible Heat Ratio Calculator.

How to Calculate Sensible Heat Ratio?

Sensible heat ratio, or SHR, expresses the fraction of total cooling devoted to sensible heat removal. Sensible cooling is associated with lowering temperature; latent cooling is associated with moisture removal on the defined process boundary.

Without a separate fan adjustment, SHR = sensible load ÷ (sensible load + latent load). If sensible load is 24,000 BTU/h and latent load is 6,000 BTU/h, total load is 30,000 BTU/h and SHR is 0.8, or 80%.

The calculator adds its fan-heat input to the sensible numerator and to the total denominator. Its specific formula is (sensible + fan heat) ÷ (sensible + fan heat + latent). This is appropriate only when the separate fan term is a real additional sensible component of the boundary being assessed.

Trane’s sensible and latent heat guide explains these capacity components and SHR. The quotient is dimensionless, but the physical meaning still depends on which loads and equipment components it includes.

Define Whether the Ratio Describes a Room or a Coil

A room load describes the cooling required at the occupied-space boundary. A coil load can also include air-system gains and outdoor-air treatment, depending on the arrangement. Those two ratios need not be identical.

Fan energy can become a sensible heat contribution in the airstream or space, but the amount and boundary depend on the system. A fan located and accounted for upstream of the cooling process can be treated differently from a fan whose heat is added after it.

Write the boundary explicitly before entering a fan value. If the source sensible load already includes fan heat, enter zero for the separate fan term. Adding it again creates a larger sensible numerator and total that do not represent a new physical load.

Likewise, check whether equipment performance data is gross or net of specified fan effects. Comparing a gross coil SHR with a net room-load SHR without reconciliation can make a seemingly close ratio misleading.

ASHRAE’s heating and cooling load chapter distinguishes room and system loads and includes fan energy among system considerations. Use the relevant accounting method rather than applying a fan allowance to every ratio automatically.

Worked Example With a Separate Fan Term

Suppose an illustrative ledger gives 24,000 BTU/h sensible load and 6,000 BTU/h latent load before a separately identified 500 BTU/h fan-heat contribution. Assume all three terms belong to the coil-side boundary being assessed.

Enter 24,000, 6,000 and 500 in the calculator. Adjusted sensible load is 24,500 BTU/h. Adjusted total is 24,500 + 6,000 = 30,500 BTU/h. SHR is 24,500 ÷ 30,500 = approximately 0.8033, displayed as 0.803.

Without the separate fan term, the original room-load ratio is 24,000 ÷ 30,000 = 0.8000. Both calculations can be valid descriptions of their stated boundaries. The difference is not evidence that the room’s moisture load changed.

Defined case Sensible component Latent component Total SHR
Original load ledger 24,000 BTU/h 6,000 BTU/h 30,000 BTU/h 0.8000
With separate included fan heat 24,500 BTU/h 6,000 BTU/h 30,500 BTU/h 0.8033
Same adjusted ledger entered directly 24,500 BTU/h plus zero extra fan 6,000 BTU/h 30,500 BTU/h 0.8033

The third row shows an equivalent input approach. It is valid only because the 500 BTU/h has already been included in the entered sensible term. Adding another 500 would count the same fan contribution twice.

Recover Sensible and Latent Components From SHR

If total load and SHR are known on a compatible boundary, sensible load is total × SHR and latent load is total × (1 − SHR). These two components should add back to the total.

For an illustrative total of 30,000 BTU/h and SHR 0.8, sensible load is 24,000 BTU/h and latent load is 6,000 BTU/h. At the same total with SHR 0.7, the components are 21,000 sensible and 9,000 latent.

A lower SHR therefore represents a larger latent fraction at a fixed total. It does not necessarily mean a larger latent rate when totals differ. A small system with low SHR can remove less moisture-related heat in absolute terms than a much larger system with higher SHR.

Do not confuse SHR with COP, EER or seasonal efficiency. SHR splits cooling capacity or load into components. Efficiency relates useful output to input energy on a defined basis. A ratio of 0.8 is not an 80% electrical conversion efficiency.

Keep load SHR and equipment capacity SHR labeled separately. A building requirement is not a product characteristic, and a product’s ratio can change with operating conditions.

Check Units, Timing and Zero-Load Cases

The input sensible, latent and fan terms must use matching rate units. This calculator labels all three in BTU/h. A fan input in electrical watts must first be translated into the relevant sensible heat rate on the selected boundary; raw watts cannot be added numerically to BTU/h.

The terms must also describe the same design condition. A morning sensible peak and an evening latent peak do not automatically form a coincident load. Use the timing treatment required by the load method.

For nonnegative components and a positive total, SHR lies between zero and one. A purely sensible case with no latent load gives 1. A purely latent case with no sensible or fan load gives 0.

If all inputs are zero, the ratio is undefined because the denominator is zero. Do not interpret that case as SHR 0, a failed unit or a meaningful design condition. Establish a positive relevant total before calculating the ratio.

Extra display decimals do not resolve uncertain load estimates. A result shown as 0.803 can reasonably be discussed as about 0.80 when the component inputs are broad planning assumptions.

Compare Equipment at the Actual Operating Conditions

A cooling unit’s sensible and latent capacities depend on entering-air conditions, airflow, outdoor temperature and operation. A single catalog SHR should not be assumed constant across every project condition.

For a hypothetical 32,000 BTU/h total capacity at SHR 0.85, sensible capacity is 27,200 BTU/h and latent capacity 4,800 BTU/h. This exceeds the original example’s total load but falls short of its 6,000 BTU/h latent requirement.

The mismatch illustrates why total capacity and SHR must be considered together. A ratio close to the load ratio does not prove adequacy if total capacity is too small, and a larger total does not guarantee enough latent capacity if the split is unsuitable.

ACCA Manual S addresses equipment selection using the calculated loads and manufacturer performance data. Use the actual matched combination and design conditions rather than a generic assumed SHR for all products.

Do not change airflow or other settings solely to chase a ratio from this calculator. Equipment operating limits, total performance and distribution requirements belong in the qualified selection or commissioning process.

Audit the Fan-Heat Accounting Before Sharing the Result

Trace the fan term back to its source. Determine whether it represents electrical input, heat delivered to the airstream or a net-capacity adjustment already applied elsewhere. Those descriptions are related but not interchangeable.

If a report supplies net sensible capacity after fan heat, do not subtract fan heat again. If a coil-load ledger already includes it, do not add it again. Draw a simple boundary note showing where the term enters the accounting.

Keep any outdoor-air or duct gains consistent in the same way. Moving from room load to coil load can involve several components, not just fan heat. Labeling the two totals makes the difference understandable.

For a final record, retain sensible load, latent load, separately added fan heat, total load and SHR together. A bare ratio loses the information needed to check both the arithmetic and the suitability of an equipment comparison.