Calculate latent cooling load by multiplying dry-air mass flow by the humidity-ratio reduction and the latent heat associated with that moisture removal. For a near-standard-density ventilation estimate in US units, this is approximately 0.68 × CFM × the humidity-ratio difference in grains per pound of dry air, yielding BTU/h.
Open the Latent Heat Load Calculator.
How to Calculate Latent Cooling Load
Latent load is the cooling work associated with removing water vapor rather than merely lowering air temperature. It matters when humid outdoor air enters a building, people release moisture, or cooking and other processes add vapor indoors.
Begin with the boundary. An outdoor-air calculation compares outdoor humidity ratio with the indoor target. A cooling-coil calculation compares the mixed air entering the coil with the air leaving it. Those are different processes, even when both are expressed in BTU/h.
The calculator above uses this expanded relationship:
Latent load = airflow × 60 × air density × (humidity-ratio difference ÷ 7,000) × latent heat of vaporization
Airflow is in cubic feet per minute. Multiplying by 60 converts the flow to cubic feet per hour. Density converts volume to mass, and dividing grains by 7,000 converts the moisture difference to pounds of water per pound of dry air.
For the simplified calculation, density is treated as representative dry-air mass per unit volume. A rigorous psychrometric calculation instead uses dry-air mass flow derived from the actual moist-air specific volume. The distinction becomes more important at unusual temperature, humidity, or elevation.
Use a psychrometric method when the estimate needs to support equipment selection. The ASHRAE Qatar cooling and heating equation reference shows the familiar standard-air sensible, latent, and total-heat forms, including the grain-based latent relationship.
Obtain Humidity Ratio Rather Than Subtracting Relative Humidity
Humidity ratio measures the mass of water vapor relative to dry air. Relative humidity measures how close the air is to saturation at its current temperature. They answer different questions.
Air at 50% relative humidity can contain very different amounts of vapor at different temperatures. Subtracting 50% indoor RH from 70% outdoor RH does not produce a 20-grain humidity difference.
For each air state, record dry-bulb temperature, relative humidity or another suitable humidity measurement, and atmospheric pressure or elevation. Use a valid psychrometric calculation or chart to obtain humidity ratio for both states at the same pressure.
Then subtract in the direction of the process. For an outdoor moisture load, use outdoor minus indoor humidity ratio. For moisture removed across a coil, use entering minus leaving humidity ratio.
If the difference is negative, the outside air is drier on a mass basis than the room. It does not impose a positive outdoor-air dehumidification load under those conditions. The calculator accepts a nonnegative difference, so do not turn a drying effect into a moisture load by entering its absolute magnitude without explaining the boundary.
| Input | Example value | Meaning |
|---|---|---|
| Outdoor airflow | 250 CFM | Air brought across the selected boundary |
| Outdoor humidity ratio | 105 grains/lb dry air | Water content of incoming air |
| Indoor target humidity ratio | 65 grains/lb dry air | Water content to maintain indoors |
| Humidity-ratio difference | 40 grains/lb dry air | Moisture that must be removed |
| Representative air density | 0.075 lb/ft³ | Standard-air approximation |
| Latent heat factor | 1,061 BTU/lb water | Assumed heat associated with removal |
The two humidity ratios in this table are illustrative psychrometric inputs. They are not universal values for outdoor and indoor conditions.
Work Through a 250 CFM Ventilation Example
Assume a building receives 250 CFM of outdoor air with a 40-grain-per-pound humidity-ratio difference. Use density of 0.075 lb/ft³ and a latent heat factor of 1,061 BTU/lb water.
First find the approximate dry-air mass flow:
250 × 60 × 0.075 = 1,125 lb dry air/h
Convert the moisture difference:
40 ÷ 7,000 = 0.005714 lb water/lb dry air
The water removal rate is therefore:
1,125 × 0.005714 = 6.429 lb water/h
Finally, multiply by the latent heat factor:
6.429 × 1,061 = 6,820.7 BTU/h
Enter 250, 40, 0.075, and 1,061 in the calculator to reproduce approximately 6,821 BTU/h. The shorter 0.68 relationship gives 6,800 BTU/h, a small difference caused by rounding the coefficient.
If these conditions persisted for eight hours, the associated latent energy would be approximately 54,566 BTU. That is an energy quantity over the period. The 6,821 BTU/h result is a rate.
The calculated water removal is also about 0.77 US gallon per hour using approximately 8.34 pounds per gallon. That conversion helps visualize the moisture burden, but a condensate drain measurement does not automatically isolate this outdoor-air contribution.
Add Moisture Sources Without Counting Them Twice
A building can have moisture sources beyond the outdoor ventilation stream. Occupants, showers, cooking, wet cleaning, stored wet materials, and process equipment may all matter.
For a separately known moisture generation rate, multiply pounds of water per hour by the same appropriate latent heat factor. An illustrative additional source of 2 lb/h contributes about 2,122 BTU/h when using 1,061 BTU/lb.
Adding that source to the ventilation example gives approximately 8,943 BTU/h. This assumes both sources occur together and are independent of the ventilation moisture already counted.
Infiltration needs particular care. A load model may already include air leakage from weather and envelope inputs. Adding another arbitrary CFM allowance for the same leakage would duplicate its latent contribution.
Exhaust replacement air also needs a coherent airflow balance. If an exhaust fan draws 100 CFM from a room, replacement air comes through some combination of designed supply, adjacent spaces, and leakage. It is not always 100 CFM of new outdoor air added on top of an independently counted outdoor-air stream.
Document whether an energy recovery device changes the incoming humidity ratio. Use the air state after the device when calculating the coil’s remaining moisture burden, rather than taking a full outdoor-to-room difference and also subtracting a guessed recovery percentage.
Separate Latent Load, Sensible Load, and Equipment Capacity
A temperature-only calculation misses latent load. Conversely, the latent calculation does not account for cooling hot outdoor air down to room temperature.
For an illustrative 250 CFM stream cooled through a 20°F temperature difference, the standard sensible relationship gives:
1.08 × 250 × 20 = 5,400 BTU/h sensible
Adding the earlier 6,820.7 BTU/h latent estimate gives about 12,220.7 BTU/h combined. Its sensible heat ratio is approximately 5,400 ÷ 12,220.7 = 0.442.
That ratio describes this example stream under the stated assumptions. It is not a required sensible heat ratio for the complete building or a fixed property of an air conditioner.
A more complete total-air process calculation uses dry-air mass flow and the entering-to-leaving enthalpy difference. It handles sensible and latent changes together on a consistent psychrometric basis.
Manufacturer equipment data must then show enough latent capacity at the intended entering-air condition, airflow, and operating mode. A unit’s nominal total tonnage does not establish its actual moisture removal under every condition. Trane’s sensible and latent heat explanation distinguishes temperature removal from moisture removal and explains why both contribute to total capacity.
Test the Assumptions That Change the Result
Airflow and humidity-ratio difference act linearly in this model. If the same 40-grain difference applies to only 150 CFM, the latent estimate falls to approximately 4,092 BTU/h. At 350 CFM, it rises to approximately 9,549 BTU/h.
Likewise, at 250 CFM, a 20-grain difference produces about 3,410 BTU/h, while a 60-grain difference produces about 10,231 BTU/h. This makes measured or properly selected design humidity conditions more useful than extra decimal places in the final answer.
Density is not a climate severity factor. Use a density or specific-volume assumption appropriate to the actual air state and elevation. Do not increase it merely because a summer day feels humid.
The latent heat factor also has a defined physical basis and varies with temperature. The calculator’s adjustable range allows a chosen approximation; it does not compensate for incorrect humidity units.
For a residential equipment decision, integrate the moisture estimate with the room and whole-house load calculation. ACCA’s Manual J overview describes the residential load-calculation framework. Record the airflow boundary, design air states, internal moisture sources, and selected equipment performance together so the latent result remains traceable to the conditions it represents.