How to Compare Heat Pump and Gas Furnace Operating Costs

Compare heat pump and gas furnace operating costs for the same delivered seasonal heat, using compatible efficiency assumptions and local energy prices. Keep electricity, gas fuel and fixed charges on clear boundaries; a positive calculator result means the modeled heat pump charge is higher.

Open the Heat Pump vs Gas Furnace Cost Calculator.

How to Compare Heat Pump and Gas Furnace Operating Costs?

Begin with useful heat delivered to the same building boundary over the same period. Do not compare one system at a larger heat demand or a different indoor temperature and attribute the resulting cost difference entirely to efficiency.

For a heat pump, electrical kWh = delivered thermal kWh ÷ seasonal average COP on the defined boundary. For a gas furnace, convert delivered heat to therm-equivalent energy and divide by the assumed seasonal fuel efficiency before applying dollars per therm.

The calculator subtracts gas fuel charge from heat pump electricity charge. A positive result means heat pump electricity costs more in the stated model; a negative result means it costs less. The sign is important because the tool does not label every positive number as savings.

Natural Resources Canada’s heat pump guide explains output/input and seasonal performance concepts. Use an appropriate seasonal ratio for an annual comparison rather than inserting one favorable point COP for the whole winter.

Establish Equal Delivered Heating Demand

The annual heating demand field uses kWh of useful heat, not billed electrical kWh. A requirement of 18,000 thermal kWh can be supplied by different systems with different input energy.

Keep domestic hot water, cooking and other services outside both sides unless the comparison intentionally includes them. A gas bill containing several services is not automatically the space-heating demand, and whole-house electricity contains unrelated loads.

The delivered boundary also matters. Heat at the furnace outlet, heat at a hydronic meter and heat delivered to occupied rooms can differ if distribution losses intervene. Align the demand and efficiency assumptions rather than combining incompatible data.

If the building will be insulated, air sealed or expanded, choose whether the scenario represents its current or proposed condition. Hold that condition constant between the two heat sources unless the comparison explicitly analyzes a combined project.

A capacity in BTU/h cannot be entered directly as annual heating energy. Seasonal demand requires a time-dependent model or suitable energy analysis. Copying a nameplate capacity into the annual field would mix rate and energy units.

Understand the Two Cost Equations

Heat pump charge = annual thermal kWh ÷ average COP × electricity rate. The average COP should represent total useful heat divided by matching electrical input over the period, rather than an unweighted average of several point COP readings.

Gas fuel charge = annual thermal kWh × 0.0341214 ÷ AFUE fraction × gas price per therm. The conversion factor expresses thermal kWh as therm-equivalent energy. One therm is 100,000 BTU.

The EIA energy conversion guide provides thermal-energy conversion context. Use the actual utility price unit; dollars per cubic foot or per Ccf cannot be entered as dollars per therm without the appropriate bill conversion.

AFUE is a seasonal fuel-use rating. Natural Resources Canada’s furnace EnerGuide guide notes that it excludes electrical energy used by fans, pumps and controls. The calculator’s furnace side is therefore a fuel charge, not automatically its complete operating cost.

The model uses one electricity rate and one gas rate. Both should be documented variable-rate assumptions appropriate to the period. It does not retrieve current tariffs or account for every billing component.

Worked Equal-Heat Comparison

Assume an illustrative annual demand of 18,000 thermal kWh, average heat pump COP of 3, electricity at an invented $0.16/kWh, gas at an invented $1.50/therm and furnace AFUE of 90%.

Heat pump electricity is 18,000 ÷ 3 = 6,000 kWh. Its charge is 6,000 × $0.16 = $960.

Delivered heat in therm-equivalent units is 18,000 × 0.0341214 = 614.1852 therm. Estimated gas input is 614.1852 ÷ 0.90 = 682.428 therm, and fuel charge is 682.428 × $1.50 = $1,023.642.

The calculator difference is $960 − $1,023.642 = −$63.642, displayed as about −$63.64 per year. The negative sign means the modeled heat pump electricity charge is lower by that amount on these boundaries.

Item Heat pump Gas furnace
Equal delivered heat 18,000 thermal kWh 18,000 thermal kWh
Efficiency assumption Average COP 3.0 AFUE 90%
Modeled purchased energy 6,000 electrical kWh 682.428 therm
Illustrative variable price $0.16/kWh $1.50/therm
Modeled energy charge $960.00 $1,023.64 fuel only

These prices and operating values are teaching assumptions, not local quotes or promised annual savings. The small difference also means omitted components and uncertain performance can materially affect the comparison.

Test Performance and Rate Sensitivity

Hold the same demand and prices but reduce average COP to 2.5. Heat pump electricity becomes 7,200 kWh and charge becomes $1,152. The difference from the same gas fuel charge is now about +$128.36, meaning the heat pump charge is higher in that scenario.

This does not establish that a particular winter will have COP 2.5 or 3.0. It shows why an appropriate seasonal performance assumption matters more than selecting one favorable rating-point value.

The simplified variable-charge break-even COP is electricity rate × AFUE fraction ÷ (0.0341214 × gas price per therm). At the example rates it is about 2.81. Above that ratio, the modeled heat pump electricity charge is lower; below it, it is higher, before omitted components.

Demand cancels from that simple break-even equation because both sides supply the same useful heat. It does not cancel from the annual dollar difference, which scales with heating energy. Nor does this equation determine an automatic outdoor-temperature switching point without performance and control information.

Add Backup and Furnace Electricity Consistently

If the entered heat pump seasonal COP already includes backup and relevant fans, do not add their electricity again. If it covers only the heat pump, separately model the backup share and its electrical or fuel input on the same delivered-heat basis.

For example, a heat pump cannot be assigned the full building heat demand while backup is also assigned that same full demand. Divide the useful heat between the sources or use a correctly measured whole-system seasonal ratio.

On the furnace side, add blower and control electricity where the comparison includes complete variable operation. An illustrative additional 120 kWh at $0.16/kWh adds $19.20 to the gas-system charge. It would change the example total to about $1,042.84 and the difference from the $960 heat pump case to about −$82.84.

That electrical figure is another teaching allowance, not a generic furnace specification. Use measured or supported operating data, and avoid adding a fan allowance to an electrical total that already includes it.

Keep Fixed Charges and Ownership Costs Separate

A gas customer charge may remain if gas still serves water heating or cooking. It should not be credited as a saving merely because space heating changes. If service removal is part of the project, evaluate the actual tariff and scope explicitly.

Electricity time-of-use periods, demand charges, tiers, taxes and adjustments can also alter the bill. The calculator’s flat rates approximate only the energy-charge boundary that the inputs represent.

Installation, maintenance, equipment life and financing are separate ownership-cost questions. A lower modeled annual energy charge does not by itself establish a purchase recommendation or payback period.

For a decision record, present energy charges, other operating components and project costs in separate lines. That makes it clear which difference comes from efficiency and rates, and which comes from another part of the project.

Retain a Comparison Another Person Can Reproduce

Record the delivered heating demand source, building condition, seasonal performance assumptions, component boundaries and dated tariff inputs. Keep the calculator’s sign convention with the result.

Compare the proposed heat pump’s capacity and operating range with the building load as a separate engineering check. A favorable cost quotient does not prove adequate winter output, distribution or backup capability.

If reasonable scenarios reverse the cost result, present that sensitivity rather than declaring one system universally cheaper. The useful output is a transparent equal-heat comparison tied to actual project information and clearly labeled assumptions.