Compare SEER2 cooling-cost savings using compatible SEER2 ratings and the same seasonal amount of heat removed. Calculate each modeled electrical-energy total first, then apply the same variable electricity rate.
Open the SEER2 Savings Calculator.
How to compare SEER2 cooling cost savings
SEER2 expresses a standard seasonal relationship between cooling delivered in BTU and electrical energy consumed in watt-hours. For a common seasonal cooling-energy quantity, modeled electrical kWh = seasonal thermal BTU / SEER2 / 1,000.
The embedded calculator expresses that common thermal quantity as reference cooling capacity × equivalent full-load cooling hours. Its hours input therefore means equivalent full-load hours, not simply elapsed hours with a compressor enabled.
Compute old and new modeled kWh on that same basis. Multiply their difference by a common variable electricity price to estimate the variable cooling-charge saving.
Both ratings must be SEER2 values for appropriate matched equipment combinations. An old SEER value should not be entered as though it were SEER2 without a documented compatible basis.
Work through a common seasonal cooling requirement
Use an illustrative reference capacity of 36,000 BTU/h and 1,200 equivalent full-load cooling hours. Their product is 43,200,000 BTU of seasonal heat removal.
Compare compatible SEER2 values of 12 and 18 at an illustrative variable rate of $0.16/kWh.
| Quantity | SEER2 12 scenario | SEER2 18 scenario |
|---|---|---|
| Common seasonal heat removed | 43.2 million BTU | 43.2 million BTU |
| Modeled electricity | 43,200,000 / 12 / 1,000 | 43,200,000 / 18 / 1,000 |
| Electrical energy | 3,600 kWh | 2,400 kWh |
| Variable charge | $576 | $384 |
The modeled electrical reduction is 3,600 – 2,400 = 1,200 kWh. The corresponding variable-charge saving is 1,200 × 0.16 = $192.
This is a transparent seasonal-rating scenario, not a guaranteed utility-bill reduction. It assumes the same cooling service, common energy basis and price for both alternatives.
The higher rating is 50% above the lower rating, but modeled electricity falls by 33.33%. Efficiency improvement and energy reduction use different denominators.
Understand equivalent full-load hours before entering them
Equivalent full-load cooling hours connect a seasonal heat-removal quantity to a chosen reference rate. They are seasonal thermal energy divided by reference thermal capacity.
If seasonal heat removal is 43.2 million BTU and the chosen reference rate is 36,000 BTU/h, the equivalent full-load hours are 1,200. The building does not need to operate at that rate for 1,200 literal clock hours.
A modulating system can run for many more elapsed hours while delivering less than full output. Conversely, simply counting thermostat calls does not establish seasonal cooling energy.
Keep the reference capacity and equivalent hours together. If the reference changes while the intended seasonal thermal energy stays fixed, the equivalent hours must change inversely.
Do not give a larger proposed unit the same equivalent hours and then claim an equal-service efficiency comparison. That would increase the modeled heat removed as well as changing the rating.
Preserve the seasonal rating procedure and equipment match
ENERGY STAR’s efficiency definitions distinguish SEER2 from SEER, EER2 and heating metrics. SEER2 is determined under the newer specified seasonal test procedure, while SEER uses a different procedure.
There is no universal conversion factor in this calculator that makes every historical SEER rating directly comparable to SEER2. Obtain compatible data for the actual equipment when an old label uses another metric.
Also identify the complete indoor/outdoor match. A rating associated with one listed combination should not automatically be assigned to a different coil, air handler or multi-zone arrangement.
A standard seasonal rating is useful for comparisons, but actual local performance can differ with weather, installation, airflow, controls and use. The calculator does not model those site effects independently.
Keep cooling ratings separate from heating performance. A higher SEER2 value does not by itself quantify winter heat-pump electricity use or low-temperature heating capacity.
Check the fractional savings with an independent ratio
For equal thermal service under the model, new electricity divided by old electricity equals old SEER2 / new SEER2. The modeled reduction fraction is therefore 1 – old SEER2 / new SEER2.
For 12 versus 18, 1 – 12 / 18 = 0.333333, or 33.33%. Applying that fraction to the old modeled $576 charge gives the same $192 saving.
This ratio check is useful for catching arithmetic and input errors. It does not require changing capacity or equivalent hours when both scenarios already share the same seasonal thermal quantity.
If both SEER2 values are equal, modeled savings are zero. If the proposed value is lower, the modeled difference becomes negative, meaning a charge increase under the stated assumptions.
Do not replace a negative result with zero merely to call the output savings. Preserve the sign and investigate whether the equipment values, service assumptions or comparison direction were entered correctly.
Apply a price compatible with the energy comparison
The EIA electricity measurement guide distinguishes energy from power. The price input here is per electrical kWh and belongs on the modeled electrical-energy difference.
At $0.08/kWh, the example’s 1,200-kWh reduction is worth $96; at $0.24/kWh it is worth $288. These are price sensitivities, not claims about current local tariffs.
Time-of-use and tiered rates can require additional modeling. A standard seasonal rating does not identify precisely which tariff intervals contain the avoided electricity.
Fixed customer charges may remain unchanged. A 33.33% reduction in modeled cooling electricity does not imply that the whole household utility bill falls by 33.33%.
State whether a price includes the relevant variable delivery and supply components. Keep demand charges, tax terms and fixed costs on their own documented boundaries rather than mixing a whole-bill average with marginal savings without explanation.
Compare actual years only after checking service and weather
A lower bill after installation does not isolate SEER2 improvement by itself. A milder summer, changed thermostat setting, new shading or different occupancy can alter cooling demand. A larger conditioned area or additional operating hours can move consumption in the opposite direction.
Keep the rating scenario distinct from a before-and-after utility study. The scenario holds thermal service fixed; a measured comparison needs an appropriate way to assess weather and service changes as well as noncooling electrical loads. A whole-home meter generally contains more than cooling electricity.
The thermal quantity should also represent the same cooling boundary. Total heat removal and sensible heat removal are different quantities when moisture removal is relevant. Using a sensible-only load for one system and total cooling energy for the other would defeat the equal-service comparison even if the SEER2 values were compatible.
Keep purchase economics outside the energy result
An equipment upgrade can have a higher initial price, different maintenance requirements or other project implications. The $192 scenario estimates only the modeled variable cooling-charge difference.
A simple payback calculation could divide an explicitly defined incremental project cost by an annual saving, but that would introduce additional assumptions about future prices, use and performance. It would not establish complete ownership cost by itself.
Likewise, incentives should be confirmed and recorded as one-time project terms rather than silently added to recurring annual electricity savings.
For a useful record, retain the two SEER2 ratings and their equipment matches, common seasonal thermal basis, equivalent-hour source, variable price and resulting kWh totals. Present the limits of the standard-rating model alongside the result.
That record makes the comparison understandable and revisable when better local energy information becomes available. It also prevents a seasonal efficiency label from being mistaken for an instantaneous power measurement.