SEER2 Savings Calculator
What this calculator measures
Illustrative annual variable cooling-charge comparison using compatible SEER2 values and a common seasonal cooling-energy basis expressed as capacity times equivalent full-load hours.
Inputs and units
Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.
| Input | Example value or available basis |
|---|---|
| Current System SEER2 | 10 |
| New System SEER2 | 16 |
| Cooling Capacity (BTU/h) | 36000 |
| Equivalent Full-load Cooling Hours (not elapsed compressor hours) | 1200 |
| Electricity Rate ($/kWh) | 0.16 |
Calculation method
Common seasonal heat removed equals reference cooling capacity times equivalent full-load cooling hours.
Divide that thermal BTU by each compatible SEER2 and by 1,000 for modeled electrical kWh, then apply the common rate.
Worked example
36,000 BTU/h times 1,200 equivalent full-load hours is 43.2 million BTU. SEER2 12 uses 3,600 modeled kWh; SEER2 18 uses 2,400. At $0.16/kWh the modeled saving is $192.
How to use the result
Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.
Limits and checks
A standard seasonal rating is not an exact site-specific prediction or instantaneous power ratio.
Both ratings must be SEER2 on compatible equipment combinations; no universal SEER conversion is supplied.
An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.