Duct Static Pressure Calculator
What this calculator measures
Calculate measured total external static pressure as signed leaving static minus signed entering static at manufacturer-specified equipment boundaries.
Inputs and units
Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.
| Input | Example value or available basis |
|---|---|
| Measured Leaving-side Static (signed in. w.c.) | 0.35 |
| Measured Entering-side Static (signed in. w.c.) | -0.25 |
Calculation method
Use signed static pressures at the correct entering and leaving locations specified for the actual equipment.
Subtract entering pressure from leaving pressure; with positive supply and negative return this equals their magnitudes added.
Compare only against the matching manufacturer rating and blower data.
Worked example
A leaving static of +0.35 in. w.c. and entering static of -0.25 in. w.c. give 0.60 in. w.c. across the declared external boundary.
How to use the result
Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.
Limits and checks
This calculator does not locate ports, measure pressure or authorize drilling equipment. A qualified technician follows the actual equipment manual.
Factory coil/filter treatment and separate components differ by rated boundary.
No universal maximum or airflow follows from pressure alone.
An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.