Square to Round Duct Calculator

Square to Round Duct Calculator

Compare a rectangular duct with a round diameter using either equal cross-sectional area or the documented empirical equal-flow/equal-friction relationship.
Round diameter for the selected equivalence:
Support this tool
Buy us a coffee
If this Square to Round Duct Calculator helped you, you can support the site with a small donation. It keeps the tools on the site free and supports ongoing improvements.
Buy us a coffee
Secure donation via Gumroad

What this calculator measures

Compare a rectangular duct with a round diameter using either equal cross-sectional area or the documented empirical equal-flow/equal-friction relationship.

Inputs and units

Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.

Input Example value or available basis
Clear Rectangular Width (in) 10
Clear Rectangular Height (in) 10
Round equivalence criterion Equal cross-sectional area; Empirical equal-flow/equal-friction equivalent diameter

Calculation method

Compare a rectangular duct with a round diameter using either equal cross-sectional area or the documented empirical equal-flow/equal-friction relationship.

Equal-area diameter is the square root of 4 width height/pi. The empirical equivalent-by-flow equation is 1.30 times (width height) to the power 0.625 divided by (width plus height) to the power 0.25.

Worked example

A clear 10 by 10 in duct has an equal-area round diameter of approximately 11.284 in. The empirical equal-flow/equal-friction equivalent is approximately 10.931 in; the criteria answer different questions.

How to use the result

Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.

Limits and checks

Keep both dimensions in the same units and verify roughness and design assumptions. A transition fitting and real installation can add pressure losses not represented by these equivalence calculations.

An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.

References and method

Table of contents