Supply Duct Size Calculator
What this calculator measures
Calculate clear supply-duct cross-sectional area from explicitly required airflow and target average velocity.
Inputs and units
Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.
| Input | Example value or available basis |
|---|---|
| Required Supply Airflow (CFM) | 1200 |
| Target Average Supply Velocity (FPM) | 700 |
Calculation method
Divide CFM by FPM for clear area in square feet, then multiply by 144 for square inches.
Select dimensions and verify pressure, noise, distribution and fan performance separately.
Worked example
1,200 CFM at 700 FPM gives about 246.857 square inches clear area; a 24 by 11 inch clear candidate has 264 square inches and about 654.545 FPM at that flow.
How to use the result
Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.
Limits and checks
The result is not a final duct recommendation or a prediction of installed airflow.
Flex compression, lining and fittings require actual geometry and pressure review rather than area multipliers.
An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.