Heating and Cooling Load Calculator
What this calculator measures
Compare separate simplified winter heating and summer cooling scenarios using an entered steady-state envelope coefficient and explicit additional load terms.
Inputs and units
Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.
| Input | Example value or available basis |
|---|---|
| Design Scenario | Winter heating; Summer cooling |
| Envelope Heat-Loss/Gain Coefficient UA (BTU/h F) | 400 |
| Winter Indoor Design Temperature (F) | 70 |
| Winter Outdoor Design Temperature (F) | 10 |
| Additional Winter Outdoor-Air Heating Load (BTU/h) | 6000 |
| Summer Indoor Design Temperature (F) | 75 |
| Summer Outdoor Design Temperature (F) | 95 |
| Other Summer Sensible Load Excluding UA Term (BTU/h) | 12000 |
| Summer Latent Load (BTU/h) | 5000 |
Calculation method
For the explicit winter scenario, calculate UA times indoor-minus-outdoor design temperature and add the separately entered winter outdoor-air heating term.
For the explicit summer scenario, calculate UA times outdoor-minus-indoor temperature, then add other sensible gains and latent load.
UA is an entered assembly sum, not inferred from floor area. Other terms must exclude the conduction already counted.
Worked example
With UA 400 BTU/h F, winter 70 F indoors and 10 F outdoors plus 6,000 BTU/h outdoor-air load gives 30,000 BTU/h. Summer 95 F outdoors and 75 F indoors plus 12,000 sensible and 5,000 latent gives 25,000 BTU/h.
How to use the result
Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.
Limits and checks
This is an educational steady-state accounting model, not full Manual J, dynamic solar load calculation or equipment selection.
Winter internal/solar gains are not credited; summer other sensible terms must be independently derived and simultaneous.
The supported scenarios require a nonnegative winter or summer temperature difference in its selected direction.
Ventilation/infiltration, moisture and other terms must be supplied on a compatible boundary without double counting.
An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.