Mini Split Sizing Calculator

Mini Split Sizing Calculator

Compare independently calculated cooling loads with matching manufacturer maximum and minimum capacities at their respective design and lower-load operating conditions.
Selected cooling capacity-to-load comparison:
Support this tool
Buy us a coffee
If this Mini Split Sizing Calculator helped you, you can support the site with a small donation. It keeps the tools on the site free and supports ongoing improvements.
Buy us a coffee
Secure donation via Gumroad

What this calculator measures

Compare independently calculated cooling loads with matching manufacturer maximum and minimum capacities at their respective design and lower-load operating conditions.

Inputs and units

Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.

Input Example value or available basis
Independently Calculated Design Cooling Load (BTU/h) 6400
Manufacturer Maximum Cooling Capacity at Matching Design Conditions (BTU/h) 8000
Independently Estimated Cooling Load at the Lower-load Condition (BTU/h) 1500
Manufacturer Minimum Cooling Capacity at That Same Lower-load Condition (BTU/h) 2000
Comparison to Display Design-condition maximum capacity / design load (%); Lower-condition minimum capacity / lower-condition load (%)

Calculation method

At design conditions divide matching manufacturer maximum cooling capacity by independently calculated design cooling load and multiply by 100.

At the separate lower-load condition divide matching manufacturer minimum cooling capacity by the independently estimated load at that same condition and multiply by 100.

Retain the conditions, sensible/total cooling definitions and exact equipment combination for each comparison.

Worked example

A 6,400 BTU/h design cooling load and 8,000 BTU/h maximum at matching design conditions give 125%. At a separate milder condition, a 1,500 BTU/h load and 2,000 BTU/h minimum give 133.33%.

How to use the result

Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.

Limits and checks

This tool compares entered values; it does not calculate room loads or predict cycling, moisture control or operating hours.

A minimum-to-load ratio above 100% means the stated minimum exceeds the stated load at that condition; it is not a complete diagnosis or universal selection limit.

Maximum and minimum capacities apply at their respective matching conditions, which may differ.

Heating loads and low-temperature heating performance require a separate mode-specific selection review.

An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.