BTU to CFM Calculator
What this calculator measures
Calculate airflow from an explicitly sensible heat-transfer rate, positive air-temperature rise and stated density/specific heat assumptions.
Inputs and units
Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.
| Input | Example value or available basis |
|---|---|
| Sensible Heat Transfer Rate (BTU/h) | 21600 |
| Positive Air Temperature Rise (F) | 20 |
| Air Density (lb/cu ft) | 0.075 |
| Air Specific Heat (BTU/lb F) | 0.24 |
Calculation method
Use Q sensible = 60 times density times specific heat times CFM times positive temperature rise.
Divide the explicit sensible rate by that coefficient and temperature rise.
Density 0.075 lb/cu ft and cp 0.24 BTU/lb F give coefficient 1.08; use actual suitable properties for other conditions.
Worked example
21,600 BTU/h of sensible heating at a 20 F rise, density 0.075 lb/cu ft and cp 0.24 BTU/lb F corresponds to 1,000 CFM.
How to use the result
Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.
Limits and checks
Total cooling capacity needs its sensible component identified first.
This is not fan selection, duct sizing, a latent-load calculation or a diagnostic airflow test.
The temperature rise and thermal rate must refer to the same boundary; zero temperature rise is invalid.
An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.