Duct Pressure Drop Calculator
What this calculator measures
Estimate round-duct friction pressure loss from airflow, clear diameter, length, air density, and an explicit Darcy friction factor.
Inputs and units
Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.
| Input | Example value or available basis |
|---|---|
| Airflow (CFM) | 1200 |
| Clear Round Duct Diameter (in) | 12 |
| Straight Duct Length (ft) | 100 |
| Documented Additional Equivalent Fitting Length (ft) | 0 |
| Air Density (lb/ft3) | 0.075 |
| Documented Darcy Friction Factor | 0.022 |
Calculation method
Estimate round-duct friction pressure loss from airflow, clear diameter, length, air density, and an explicit Darcy friction factor.
Convert CFM to cubic metres per second, feet and inches to metres, and density to kg/m3. Calculate velocity from circular area, then use delta-p = f(L/D) rho v squared/2. Convert pascals to inches of water using 249.08891 Pa per inch.
Worked example
At 1200 CFM, 12 in clear diameter, 100 ft straight length, no added equivalent length, 0.075 lb/ft3, and Darcy f=0.022, estimated friction loss is approximately 0.32 inches of water.
How to use the result
Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.
Limits and checks
Use a Darcy factor, not a Fanning factor. Compressibility, leakage, fittings represented by other methods, accessories, and the equipment pressure boundary are not automatically included.
This is a defined segment-loss model, not a measurement of total external static pressure. Verify the full design and manufacturer performance data.
An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.