HVAC Branch Duct Size Calculator
What this calculator measures
Estimate an ideal round branch diameter from design airflow and an explicitly selected velocity target. This is an area/velocity calculation, not a full friction design.
Inputs and units
Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.
| Input | Example value or available basis |
|---|---|
| Required Branch Airflow (CFM) | 100 |
| Explicit Design Velocity (ft/min) | 700 |
Calculation method
Estimate an ideal round branch diameter from design airflow and an explicitly selected velocity target. This is an area/velocity calculation, not a full friction design.
Required cross-sectional area is CFM divided by feet per minute. Round diameter in feet is the square root of 4 area/pi; multiply by 12 for inches.
Worked example
For 100 CFM and a selected 700 ft/min target, area is 0.142857 square feet and ideal round diameter is approximately 5.118 in.
How to use the result
Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.
Limits and checks
Select the velocity from an appropriate design process. Standard size, fittings, available static pressure, balancing, and noise checks can change the final selection.
An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.