HVAC CFM Calculator

HVAC CFM Calculator

Estimate cooling airflow from a matched sensible capacity and explicit supply-to-room temperature difference.
Airflow from the stated sensible cooling balance:
Support this tool
Buy us a coffee
If this HVAC CFM Calculator helped you, you can support the site with a small donation. It keeps the tools on the site free and supports ongoing improvements.
Buy us a coffee
Secure donation via Gumroad

What this calculator measures

Estimate cooling airflow from a matched sensible capacity and explicit supply-to-room temperature difference.

Inputs and units

Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.

Input Example value or available basis
Total Cooling Rate on the Selected Boundary (BTU/h) 36000
Matched Sensible Heat Ratio (fraction) 0.75
Room or Return Temperature on Same Boundary (F) 75
Supply Temperature on Same Boundary (F) 55
Air Density (lb/ft3) 0.075
Air Specific Heat (BTU/lb F) 0.24

Calculation method

Estimate cooling airflow from a matched sensible capacity and explicit supply-to-room temperature difference.

Sensible capacity is total cooling rate times the matched sensible heat ratio. Divide by 60 times density times specific heat times room-minus-supply temperature difference.

Worked example

36,000 BTU/h total cooling at SHR 0.75 gives 27,000 BTU/h sensible. At 0.075 lb/ft3, specific heat 0.24 BTU/(lb F), and a 20 F difference, required flow is 1,250 CFM.

How to use the result

Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.

Limits and checks

This is a sensible air-side balance, not a universal CFM-per-ton rule or a complete equipment selection.

SHR, total output, temperatures and airflow boundary must describe compatible conditions.

Latent performance, coil airflow limits, duct resistance, fan operation and room distribution need separate checks. Nonpositive cooling difference has no valid finite result.

An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.