What this calculator measures

Estimate moist-air specific enthalpy on a dry-air mass basis from 32 to 122 F using relative humidity and an altitude-based standard-atmosphere pressure estimate.

Inputs and units

Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.

Input Example value or available basis
Dry-Bulb Temperature (F; 32 to 122) 75
Relative Humidity (%) 50
Elevation for Standard-Atmosphere Estimate (ft) 0

Calculation method

Estimate moist-air specific enthalpy on a dry-air mass basis from 32 to 122 F using relative humidity and an altitude-based standard-atmosphere pressure estimate.

The saturation-pressure relationship is the ASHRAE liquid-water branch used in PsychroLib. Vapor pressure is RH fraction times saturation pressure. Humidity ratio is 0.621945 pv/(p-pv). IP enthalpy is 0.240 T + W(1061+0.444 T). Atmospheric pressure and vapor pressure both use pascals, and altitude is converted from feet to metres before the pressure estimate.

Worked example

At 75 F, 50% RH, and sea-level standard pressure, the result is approximately 28.107 Btu/lb of dry air. Dry air at the same temperature has an enthalpy of 18.000 Btu/lb on this reference basis.

How to use the result

Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.

Limits and checks

This restricted liquid-water model excludes subfreezing conditions. Actual station pressure can differ from standard atmosphere, and relative-humidity measurements need suitable accuracy.

Do not compare values using different mass or reference-temperature conventions. The calculation does not diagnose an HVAC fault.

An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.