CFM to BTU Calculator
What this calculator measures
Calculate sensible heat transfer from matched average airflow, the operating-mode temperature difference, and explicit air properties.
Inputs and units
Keep all entries on the measurement boundary and unit convention stated below. Example values are editable calculation inputs, not specifications for your equipment or a particular production job.
| Input | Example value or available basis |
|---|---|
| Measured Average Airflow (CFM) | 1200 |
| Supply Air Temperature (F) | 55 |
| Return Air Temperature (F) | 75 |
| Operating mode | Cooling: return minus supply; Heating: supply minus return |
| Air Density (lb/ft3) | 0.075 |
| Air Specific Heat (BTU/lb F) | 0.24 |
Calculation method
Calculate sensible heat transfer from matched average airflow, the operating-mode temperature difference, and explicit air properties.
The rate is 60 times density times specific heat times CFM times the positive temperature difference for the chosen mode. At 0.075 lb/ft3 and 0.24 BTU/lb F, the coefficient is 1.08.
Worked example
At 1200 CFM, return air 75 F, supply air 55 F, and the stated standard example air properties, sensible cooling is 1.08 times 1200 times 20 = 25920 BTU/h.
How to use the result
Select the output quantity you need, enter compatible values, and compare the result with the independently worked example. Where the form offers several output choices, read the units in that choice; different physical quantities must not be combined into one total.
Limits and checks
This is sensible heat only. Moisture removal and total cooling require additional psychrometric information. Mismatched temperatures, nonrepresentative velocity, and air-density changes can affect the result.
An undefined or out-of-domain combination produces a calculation-failure message. Check the positive denominators, stated input ranges, and any required matching basis before changing the calculation inputs.